E6582233
E-23
5
7) The maximum length of wires between the inverter and motor is 30 meters. If the wires are longer than 30
meters, set standard auto-tuning with the wires connected to improve low-speed torque during sensorless
vector control.
However the effects of voltage drop cause motor-generated torque in the vicinity of rated frequency to be
somewhat lower.
8) When a reactor is connected between the inverter and a motor, the motor's generated torque may fall.
Setting auto-tuning may also cause a trip () rendering sensorless vector control unusable.
5.12 Manual torque boost - increasing torque boost at low
speeds
 : Torque boost 1
Function
If torque is inadequate at low speeds, increase torque by raising the torque boost rate with this
parameter.
Output voltage
[V]/(%)
Base frequency voltage
Output frequency (Hz)

Base frequency


[Parameter setting]
Title Function Ad
j
ustment ran
g
e Default settin
g

Torque boost value 1 0.0 - 30.0 (%)
According to model
(
Refer to section 10.4
)
Valid when  is set to 0 (V/F constant) or 1 (square reduction)
Note 1: The optimum value is programmed for each inverter capacity. Be careful not to increase the torque boost
rate too much because it could cause an overcurrent trip at startup.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3E and is the answer not in the manual?

Toshiba TOSVERT VF-nC3E Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-nC3E
CategoryInverter
LanguageEnglish

Related product manuals