EasyManua.ls Logo

Toshiba TOSVERT VF-nC3E - Base Frequency; Base Frequency Voltage

Toshiba TOSVERT VF-nC3E
252 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6582233
E-16
5
5.10 Base frequency
 : Base frequency 1
 : Base frequency voltage 1
Function
Set the base frequency and the base frequency voltage in conformance with load specifications or the
base frequency.
Note: This is an important parameter that determines the constant torque control area.
Output voltage [V]
Base frequency voltage


Output frequency (Hz)
0
If  or  is changed and  trip occur at the frequency that is higher than , the following remedies
are effective.
Increase the deceleration time .
If overvoltage limit operation  is set to 0,2 or 3, decrease the over voltage stall protection level
 (ex.  =  )
[Parameter setting]
Title Function Adjustment range
Default setting

Base frequency 1 20.0-400.0 (Hz) 50.0

Base frequency voltage1 50-660 (V) 400

Table of Contents

Related product manuals