EasyManua.ls Logo

Toshiba TOSVERT VF-nC3E - Operation Frequency; Starting Frequency; Starting Frequency Setting; Run;Stop Control with Frequency Setting Signals

Toshiba TOSVERT VF-nC3E
252 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6582233
F-18
6
Starting frequency 
Output frequency (Hz)
0
Operation signal (F-CC)
Time
ON
OFF
6.7 Operation frequency
6.7.1 Starting frequency
 : Starting frequency setting
Function
The frequency set with
 is put out as soon as operation is started.
Use the
 parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title Function Ad
j
ustment ran
g
e Default settin
g

Starting frequency setting 0.1-10.0 (Hz) 0.5
6.7.2 Run/stop control with frequency setting signals
 : Operation starting frequency
 : Operation starting frequency hysteresis
Function
The Run/stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title Function Ad
j
ustment ran
g
e Default settin
g
 Operation starting frequency 0.0- (Hz) 0.0
 Operation starting frequency hysteresis 0.0- (Hz) 0.0
0 A B 100% Frequency command value
 + 
 - 

When the frequency command signal
reaches the B point, the invert er
operates.
When decelerating, operation stops
when the frequency setting signal is less
than point A.
Output frequency [Hz]


Table of Contents

Related product manuals