Function Folder name Description Status
CODESYS
program
Automatic
device
restart
Backup 2 BACKUP_2 Save the CODESYS application and device data from
the device on the USB stick.
The following files are stored on the USB stick:
n All *.app and *.crc files
n PlcLogic folder
n Folder USB_Data
n IP address
n PROFINET Device Name
n Retain data (retain.bin)
Existing files with the same name are overwritten. All
other files remain unchanged.
The names of the CODESYS application and the file
names of the boot application (*.app and *.crc) must
be the same. If the names are different or have been
changed, the application cannot be started.
RUN No
Read user
data
USB_DATA Save the "USB_Data" folder from the device on the
USB stick.
The following files are stored on the USB stick:
n CODESYS recipes and/or log files
Existing files with the same name are overwritten. All
other files remain unchanged.
The names of the CODESYS application and the file
names of the boot application (*.app and *.crc) must
be the same. If the names are different or have been
changed, the application cannot be started.
RUN No
Write access – functions
The following table describes the executable functions:
Function Folder name Description Status
CODESYS
program
Automatic
device re-
start
Restore 1 RESTORE_1 Load the CODESYS application from the USB stick into the
device.
The function can only be used if the data on the USB stick
comes from a device with identical firmware version.
The following files are loaded from the storage device to the
device:
n All *.app and *.crc files
n PlcLogic folder
The folder may only contain one application file (*.app).
All previous applications on the device will be deleted
without further warning.
The names of the CODESYS application and the file names of
the boot application (*.app and *.crc) must be the same. If
the names are different or have been changed, the applica-
tion cannot be started.
The device automatically restarts when the USB stick is re-
moved from the USB port.
STOPP yes

Table of Contents

Other manuals for turck TBEN-L Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the turck TBEN-L Series and is the answer not in the manual?

turck TBEN-L Series Specifications

General IconGeneral
Brandturck
ModelTBEN-L Series
CategoryI/O Systems
LanguageEnglish

Related product manuals