V02.00 | 2019/11
77
7.4 Commissioning TBEN-L…PLC-… as Cloud gateway
To transmit data to the Turck Cloud, the TBEN-L...PLC-... must be integrated into an Ethernet
network with Internet access. Access can be via any Internet router. Port 443 (SSL) must be en-
abled in the Internet router for the connection with the Turck Cloud.
Application example
NOTE
In Dual MAC mode, the connected networks are separated from each other by sep-
arating the Ethernet ports. For security reasons, Turck therefore recommends oper-
ating the TBEN-L...PLC-... in Dual MAC mode in cloud applications in order to separ-
ate the automation network from the Internet.
n TBEN-L…PLC-… (firmware version ≥ 1.4.6.0):
DUAL MAC mode activated [}26], the TBEN-L PLC is a member of 2 separate Ethernet net-
works
n IP addresses:
– Ethernet port P1 (locale network):
192.168.1.100, assigned via Turck Service Tool [}28]
– IP address for Ethernet port P2 (internet):
192.168.83.43, assigned via DHCP server in the network
Fig.81: Webserver – Ethernet port settings