Fig.79: Processor load in %
CODESYS-exception "ProcessorLoadWatchdog"
In case of a PLC load of approximately 80 %, CODESYS generates the exception ProcessorLoad-
Watchdog. The TBEN-L…-PLC-… remains in Stop.
Reasons for the processor overload of the TBEN-L…-PLC-… may be:
n Max. number of Devices/Slaves exceeded
n Max. number of process data exceeded
n Too low cycle times set for the number of connected devices .