12-15
Pressure • Low pressure : 1.5~2.0 kg/
• High pressure: 14.5~15.0 kg/
Estimate Refrigerant condition good
•Air conditioning good
• Normal air conditioning system
1.Normal
Pressure Low pressure : 0.8 kg/(Low)
High pressure: 8~9 kg/(Low)
Situation Deficient of air conditioning
(Air duct is not cool)
Many bubbles at sight glass
Cause Refrigerant leakage in the air
condition
Clogged the expansion valve
clogged the receiver drier
Estimate Deficient of refrigerant and leakage in
the air conditioning system
Remedy Replenish the refrigerant and repair
partially
Repair the expansion valve and the
receive drier or replace
2. Deficient of Refrigerant Gas
Pressure Low pressure : 2.5 kg/(High)
High pressure: 20 kg/(High)
Situation Refrigerant condition is not good
Never seen the bubble at sight glass
Cause Much refrigerant
Defect of the condenser
Estimate Overcharged the refrigerant
Defect of the condenser: Pin and the
cooling fan
Remedy Deflate the refrigerant
Clean the condenser,and check the
cooling fan belt
3.Too much the refrigerant