Configuration and Programming
February 2011 3-22 P/N 06-237041-001
The activation of any initiating device will activate the outputs in the general-alarm list.
Note: SLC devices are also automatically registered and configured for operation by the AutoLearn or
AutoSetup Routines, or by a configuration upload via the FenwalNET 8000-ML Configuration
Software.
Exception: AIMs require additional configuration via the LaserNET
TM
software, APICs require
additional configuration via the AIR-Intelligence
TM
Remote Configuration Software and AAMs require
additional configuration via the SET Menu or the FenwalNET 8000-ML Configuration Software after
an AutoLearn Procedure. Refer to Figure 3-20 to configure AAMs via the SET Menu.
Wait for each SLC device to report a "Not-Registered" trouble message and ensure that all these
trouble messages have been acknowledged before proceeding with the Registration Procedure.
Execute the De-Registration prior to re-registering any previously-registered addresses.
15 De-Registration. Manually De-Register SLC Devices.
Purpose: To remove one or more SLC devices from the FenwalNET 8000-ML control unit’s
configuration memory. The de-registered device(s) must be physically removed from the SLC prior
to or following the execution of the De-Registration Procedure.
16 Program Device Blink Control. Disable the Flashing LEDs on SmartOne Detectors.
Purpose: To prevent one or more SmartOne detector LEDs from flashing in standby operation. LEDs
will only illuminate in alarm condition. The detectors' default-LED operation is flashing.
17 Program Device Blink Control. Enable the Flashing LEDs on SmartOne Detectors.
Purpose: To enable one or more SmartOne detector LEDs to resume flashing in standby operation.
The flashing LEDs were disabled in a prior blink-control operation.
Monitor Modules (AIMs) Alarm-Initiating Device
Latching Operation
Activates General-Alarm List
Monitor Modules (AAMs) Alarm-Initiating Device
Latching Operation
Activates General-Alarm List
Relay Modules (AOs) Non-Silenceable Operation
In General-Alarm List
Control Modules (ASMs) Non-Silenceable Operation
Enabled for Drill Activation
Activates in Walk Test
Remote Release Modules
(RRMs)
Solenoid, On Until Reset
CAUTION
The Registration Procedure shall not be used to configure a system. It is primarily a
procedure to create a database of SLC devices. Owner locations are not assigned during
the Registration Procedure.
CAUTION
Remove all references to the de-registered devices from the system's EOC program.
SLC Device Default Operating Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security FenwalNET 8000-ML and is the answer not in the manual?

UTC Fire and Security FenwalNET 8000-ML Specifications

General IconGeneral
BrandUTC Fire and Security
ModelFenwalNET 8000-ML
CategoryControl Unit
LanguageEnglish