Configuration and Programming
P/N 06-237041-001 3-23 February 2011
Figure 3-22. FenwalNET 8000-ML Set Menu Functions (Cont’d - Fig. 6 of 14)
FOOTNOTES (Figure 3-22):
6 SLC Devices. Change an SLC Device Address.
Purpose: To create or change an SLC device address using the FenwalNET 8000-ML keypad. All SLC
devices are shipped with the default address of 000. This address must be changed to a valid address
in the range 1 to 255 before the device can be used on the SLC. Only one device with address 000 can
be connected to the SLC when using this procedure to initially address a new device. This procedure
can also be used to re-address a previously addressed device. Be sure to de-register the previous
address after the device is re-addressed.
Note: An SLC device can only have its address changed if it is not in either a trouble or alarm
condition.
18 Replace Drive. Replace an SLC Device.
Purpose: To replace an existing device on an SLC with a new device.
Note: Before selecting to “Replace Device”, remove the “old” device and connect the “new” device to
the SLC. The “old” device must report as “trouble open” and the “new” device must report as
“unregistered” to ensure that the devices have different addresses.
3. SET
3. SLC Devices
Cont’d
*
6. Replace Device
Replace SLC Device
Address of Replacement Device:*___ (1-255)
1: Keep Current Settings 2. Set Default
*=
Level-2 (Installer) Password required .
6
18
Replace SLC Device
Address to be Replaced:*___ (1-255)
SLC Module Selection
Enter SLC Module Number (1-8):_*