The value measured by the sensor is offset by the value that has been set. This com-
pensates for external influences on temperature.
Adjustment range for room temperature offset: -3.0 to +3.0 K.
Adjustment range for outside temperature offset: -3.0 to +3.0 K.
The "All" presetting means that the operating mode can only be changed or set
from the basic display (by pressing the "Operating mode" soft-key button).
If this is not selected, the operating modes for the zones can be set either using the
"Menu > Basic setting > Operating mode" selection button or from the basic display
using the "Operating mode" selection button.
Difference:
The "Operating mode" selection button can be used to directly select the operating
mode that the competent person has preset for a particular zone (All, Zone1,
Zone2, Zone3)
*1
The "Menu > Default setting > Operating mode" selection button can be used to se-
lect and set the operating mode for each zone separately.
Assigning the zones to sections can help the user program the system correctly/use
the correct settings.
This is where the operating mode for heat recovery can be set. There are three options
to choose from: "Auto", "Activate" and "Off".