multiMATIC 700/2
Notes
10/2015 79 Training 0020228700_00
The screed-drying function is used to "heat dry" newly laid heating screed in line with
regulations.
This function is available for all heating circuits.
The flow temperature is adjusted independently of the outside temperature as
shown in the following table:
Day after starting the func-
tion
Target flow temperature for this day
1
25 °C
2
30 °C
3
35 °C
4
40 °C
5
45 °C
6 - 12
45 °C
13
40 °C
14
35 °C
15
30 °C
16
25 °C
17 - 23
10 °C
(frost protection function, pump in operation)
24
30 °C
25
35 °C
26
40 °C
27
45 °C
28
35 °C
29
25 °C
The display shows the operating mode with the current day and target flow tempera-
ture. The current day can be set manually. When the function is started, the current
time of the start is saved. The day is changed exactly at this time. After the mains is
switched off/on, screed-drying starts with the last active day.
Screed-drying function