Document: LT0344 Vigilant MX1 Operator Manual
Issue 2.4 8 August 2017 Page 11-13
Point
Point Description
Description
246.1.5
Micro Test
This point is placed into fault when the Remote FBP micro test
fails.
246.1.6
CRC Fail
This point is placed into fault when the Remote FBP program
CRC check fails.
246.1.7
RAM Test
This point is placed into fault when the Remote FBP RAM test
fails.
246.1.8
Channel A
This point is placed into fault when communication channel A is
detected to be in fault. Currently not implemented.
246.1.9
Channel B
This point is placed into fault when communication channel B is
detected to be in fault. Currently not implemented.
246.1.10
Access Level 2
This point determines whether the menu for the Remote FBP will
be in Access Level 2. If the operate state is true, menu level 2
access is enabled.
246.1.11
Alarm Buzzer
This point shows the state of the alarm buzzer on the Remote
FBP, which is controlled directly by internal logic. ActInput
indicates that the alarm buzzer is active.
246.1.12
Fault Buzzer
This point shows the state of the fault buzzer on the Remote FBP,
which is controlled directly by internal logic. ActInput indicates
that the fault buzzer is active.
246.1.13
LCD Fault
This point is placed into fault when the Remote FBP LCD fails.
246.1.14
Buzzer Disable
This point indicates as Disabled when the buzzer has been
disabled, and TestOp when the buzzer is muted.
246.2.0
through
to
246.19.0
Switch Input n
This point is placed into ActInput if switch input n on the keypad is
active.
246.20.0
through
to
246.35.0
Open Collector
Output n
This point drives the open collector output n on the Remote FBP.
Its operate state can be driven by the mapped zone's operate
state or by logic.
246.36.0
FRC Monitor
This point is placed into fault when the FRC to the 26 way Switch
Input connector is removed.
246.36.1
Switch Input set 0
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 0, which contains
inputs 16-18, for NZ RFBPs this includes brigade keyswitches.
246.36.2
Switch Input set 1
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 1, which contains
inputs 1-3.
246.36.3
Switch Input set 2
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 2, which contains
inputs 4-6.
246.36.4
Switch Input set 3
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 3, which contains
inputs 7-9.
246.36.5
Switch Input set 4
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 4, which contains
inputs 10-12.
246.36.6
Switch Input set 5
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 5, which contains
inputs 13-15.
246.37.0
Fire Protection
Active
When this point is placed into the Operate state by a logic
equation the corresponding indicator on the Remote FBP turns
ON.