5. PROGRAMMING
38 D-303222 PowerMaster-10/30 G2 Installer's Guide
Configuration Instructions
When "ON", a “latchkey” message will be reported by voice
1
or SMS message to users (see
Note) upon disarming by a “latchkey user” (users 5-8 or keyfob transmitters 5-8 in PowerMaster-
10 G2 system / users 23-32 or keyfob transmitters 23-32 in PowerMaster-30 G2 system). This
mode is useful when parents at work want to be informed of a child’s return from school.
Options: OFF (default) and ON.
Notes:
To enable the reporting, you must configure the system to report "alrt" events to Private users
(Latchkey belongs to the "alerts" group of events). Refer to section 5.6.4 "REPORTED
EVENTS" option in both "
VOICE REPORT
" & "
SMS REPORT
" menus.
Latchkey Arming is supplemental in UL installations.
Certain regulations require that when the system is armed in AWAY mode, it may not be
disarmed from the outside of the house (such as by keyfobs) before entering the protected
premises and activating an "Entry Delay" zone. To answer this requirement, the PowerMaster
provides you with the following configurable options to disarm the system:
A: At "any time" (default), the system can be disarmed at all times from all devices.
B: During entry delay, the system can be disarmed only using keyfob or prox operated
devices ("on entry wrless").
C: During entry delay by code, the system can be disarmed only using PowerMaster panel
keypad ("entry + away kp.").
D: During entry delay, the system can be disarmed using keyfobs or by code using the
PowerMaster panel keypad ("on entry all.").
Determine that, when activated, the Arming Key will arm AWAY or HOME.
Options: arm AWAY (default) and arm HOME.
Note: Arming Key not to be enabled in UL Listed product.
5.5.3 Configuring Zones Functionality
The following table provides you with a detailed description of each option and its configuration settings. To select an
option and change its configuration – refer to section 5.5.1.
Configuration Instructions
Define the number of times a zone is allowed to initiate an alarm within a single
arming/disarming period (including tamper & power failure events of detectors, etc.). If the
number of alarms from a specific zone exceeds the programmed number, the control panel
automatically bypasses the zone to prevent recurrent siren noise and excessive reporting to
the Monitoring Station. The zone will be reactivated upon disarming, or 48 hours after having
been bypassed (if the system remains armed).
Options: after 1 alarm (default); after 2 alarms (default in USA); after 3 alarms and no stop.
1. CP-01 was tested and certified by ETL/Intertek.
2. CP-01 features not to be enabled in UL Listed product.
Define whether cross zoning will be active "ON" or inactive "OFF" (default). Cross zoning is a
method used to counteract false alarms - an alarm will be initiated only when two adjacent
zones (zone couples) are violated within a 30-second time window.
This feature is active only when the system is armed AWAY and only with respect to the
following zone couples: 18+19, 20+21, 22+23, 24+25, 26+27 in PowerMaster-10 G2 system /
40+41, 42+43, 44+45, 46+47, 48+49, 50+51, 52+53, 54+55, 56+57, 58+59, 60+61, 62+63 in
PowerMaster-30 G2 system.
1. If one of the two crossed zones is bypassed (see Section 5.5.2), the remaining
zone will function independently.
2. It is recommended that crossed zones will be only zones used for detection of
burglary i.e. "Zone Types": Entry/ Exit, Interior, Perimeter and Perimeter follower.
Refers to PowerMaster-30 G2 with voice option only