5. PROGRAMMING
D-303222 PowerMaster-10/30 G2 Installer's Guide 43
"SUPERVISION"
Options: after 1/2/4/8/12 (default) hour(s); and disabled.
Notes:
1. To comply with EN requirements, 1 hour or 2 hours must be selected.
2. For UL installations, set to “4 hours” or less.
3. For UL/ULC Residential Fire and Burglary Installations, the wireless supervision window
shall be enabled. It shall be set to 4 hours or less for Fire Installations and it shall be set to
24h for Burglary Installations only.
63:NOT READY
Define that in case of a supervision problem (i.e. a device is "missing" - see "62: MISSING
REPRT") whether the system will continue to operate as normal or the system status will
become "Not Ready" (upon missing) for as long as the "Missing" trouble exists.
Options: normal (default) and if missing dev.
64:MISS/JAM ALRM
Previously known as
"BELL/REP.OPT"
"EN/UL standards" require that if a supervision (missing) or jamming trouble occurs during
AWAY arming, the siren will sound and the event will be reported as a tamper event.
Define whether the system will behave according to EN standards or as normal (default).
Note: To comply with EN requirements "EN standard" must be selected.
5.5.8 Configuring Miscellaneous Features
The following table provides you with a detailed description of each option and its configuration settings. To select an
option and change its configuration refer to section 5.5.1.
Option
Configuration Instructions
91:USER PERMIT
User Permission enables you to determine whether access to the INSTALLER MODE requires
the user's permission or not. If you select enabled, the installer will be able to access the system
only through the user menu after the user code has been entered (see section 5.2).
Options: disable (default) or enable (default in UK).
Note: To comply with EN requirements, "Enable" must be selected.
92:BATTERY TYPE
1
Define which type of battery pack is used for the system to supply proper charge current.
Options: 7.2V NiMH (default) or 9.6V NiMH (default in UK).
5.6 Communication
5.6.1 General Guidance "Communication" Flow-Chart & Menu Options
The COMMUNICATION menu enables you to configure and customize the communication and reporting of alarm,
troubles and other system events for monitoring companies or private users according to your local requirements and
personal preferences. PowerMaster offers a variety of communication means including telephone PSTN landline,
Cellular GSM, GPRS or SMS and IP via broadband internet connection.
Notes:
1. GPRS cannot be enabled in UL Listed product.
2. SMS is a supplementary feature.
The "04.COMMUNICATION" menu contains several sub-menu options, each covering a group of configurable features
and parameters related to the communication and reporting as follows (see detailed list in Step 3 of the chart below):
Option
Description of Option Features and Parameters
Section
1:PSTN TEL LINE
Contains configurable features and parameters related to the PSTN telephone line
to which the PowerMaster is connected.
5.6.2
2:GSM/GPRS/SMS
Contains configurable features and parameters related to the Cellular connection
of the PowerMaster system.
5.6.3
3:C.S.REPORTING
Contains configurable features and parameters related to Reporting of event
messages to Monitoring Stations via telephone, cellular or IP broadband
communication.
5.6.4
4:PRIVATE REPORT
Contains configurable features and parameters related to Reporting event
messages to Private Users via telephone or SMS.
5.6.5
1
Refers to PowerMaster-30 G2 only

Table of Contents

Other manuals for Visonic PowerMaster-10 G2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Visonic PowerMaster-10 G2 and is the answer not in the manual?

Visonic PowerMaster-10 G2 Specifications

General IconGeneral
ModelPowerMaster-10 G2
CategorySecurity System
Wireless TechnologyPowerG
Remote ControlYes
Event Log1000 events
CommunicationGSM, PSTN, IP
Frequency868 MHz
TypeWireless
Operating Temperature-10°C to +55°C
HumidityUp to 85% non-condensing

Related product manuals