44 D-302756
4.
5.
or
Select between "no act disable", "3 h", "6 h", "12 h", "24 h", "48 h",
and "72 h".
6.
You can now press the or button to program any other
menu in "
DEFINE PANEL
" or press the button to take you to "
<OK>
TO EXIT
".
4.8.4 Configuring Alarm Cancel Period
Here you determine the ”cancel alarm” period that starts upon reporting an alarm to the Monitoring Station. If the
user disarms the system within that time period, a “cancel alarm” message is sent to the Monitoring Station.
Available options are: cancel time 1 m, cancel time 5 m (default), cancel time 15 m, cancel time 60 m,
cancel time 4 hours and also cancel inactive (default in USA).
Note: To comply with CP-01 requirements, "1 minute" option is not available
.
To Configure the Alarm Cancel Period
1.
Repeat steps 1 to 4 of section 4.2 "Entering the Installer Menu".
2.
3.
or
4.
5.
or
Select between "cancel time 1 m", "cancel time 5 m", "cancel time
15 m", "cancel time 60 m", "cancel time 4 h", and "cancel
inactive".
6.
You can now press the or button to program any other
menu in "
DEFINE PANEL
" or press the button to take you to "
<OK>
TO EXIT
".
4.8.5 Configuring Power Failure Threshold Period
Here you determine the time interval between AC power failure occurrence and the failure reporting.
Options: 5 minutes (default), 30 minutes, 60 minutes or 180 minutes.
Note: To comply with EN requirements, set to 60 min. max.
06:ALARM CANCEL
cancel time 5 m
06:ALARM CANCEL
01:ENTRY DELAY 1
DEFINE PANEL
21:NOT ACTIVE
no act disable
21:NOT ACTIVE