EasyManuals Logo

Visonic POWERMASTER-10 - INSTALLER GUIDE User Manual

Visonic POWERMASTER-10 - INSTALLER GUIDE
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
D-302756 45
To Configure the Power Failure Threshold Period
1.
Repeat steps 1 to 4 of section 4.2 "Entering the Installer Menu".
2.
3.
or
4.
5.
or
Select between "5 minutes", "30 minutes", "60 minutes", and "180
minutes".
6.
You can now press the or button to program any other
menu in "
DEFINE PANEL
" or press the button to take you to "
<OK>
TO EXIT
".
4.8.6 Configuring Abort Time
Here you select the length of time allowed by the system to abort an alarm (not applicable to alarms from FIRE, 24H
SILENT and EMERGENCY zones). The PowerMaster-10 is programmed to provide an “abort interval” that starts upon
detection of an event. During this interval, the buzzer sounds a warning but the siren remains inactive and the alarm is
not reported. If the user disarms the system within the allowed abort interval, the alarm is aborted.
Available options are: 00s (default in USA), 15s, 30s (default), 45s, 60s, 2m, 3m and 4m.
Note: To comply with CP-01 requirements, "60s", "3m" and "4m" options are not available
.
Note: To comply with UL requirements, the abort time must not exceed 45 sec
.
To Configure the Abort Time
1.
Repeat steps 1 to 4 of section 4.2 "Entering the Installer Menu".
2.
3.
or
4.
5.
or
Select between "abort time 00s", "abort time 15s", "abort time
30s", "abort time 45s", "abort time 60s", "abort time 2m",
"abort time 3m" and "abort time 4m".
6.
You can now press the or button to program any other
menu in "
DEFINE PANEL
" or press the button to take you to "
<OK>
TO EXIT
".
05:ABORT TIME
abort time 30s
05:ABORT TIME
01:ENTRY DELAY 1
DEFINE PANEL
34:AC FAIL REP
5 minutes
34:AC FAIL REP
01:ENTRY DELAY 1
DEFINE PANEL

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Visonic POWERMASTER-10 - INSTALLER GUIDE and is the answer not in the manual?

Visonic POWERMASTER-10 - INSTALLER GUIDE Specifications

General IconGeneral
CategorySecurity System
ModelPOWERMASTER-10
Wireless ProtocolPowerG
Backup BatteryYes
User CodesUp to 48 user codes
TypeWireless Alarm System
Partitions3
CommunicationGSM
Wireless Frequency868 MHz
KeypadsUp to 8 keypads
Event Log1000 events
Power SupplyExternal power supply
Backup Battery Voltage7.2V
Operating Temperature-10°C to +50°C
Humidity85% non-condensing
ZonesUp to 30 wireless zones

Related product manuals