Watlow EZ-ZONE
®
PMI Controller • 158 • Chapter 7 Profiling Page
Configuring the Function Key to Start and Stop a Profile
1. Navigate to the Setup Page and then the Function menu. From the Home Page, press and
hold the ¿ or Down ¯ key for approximately six seconds where the upper display will
show ai and the lower display will show SEt.
2. Press the Up ¿ or Down ¯ key to navigate to the Function FUn menu.
3. Press the Advance Key ‰ to enter this menu. The upper display will show 1 and the lower
display will show fUn.
4. Press the Advance Key ‰ to select the level. The upper display will show high and the
lower display will show LEv.
5. Press the Up ¿ or Down ¯ keys to select the level that will start the prole (high or
low).
6. Press the Advance Key ‰ to select the function. In this example, select Prole Start /
Stop p.sts.
7. Press the Advance Key ‰ to select the function instance (Prole to start).
8. Return to the Home Page by pressing and holding the Innity Key ˆ for approximately
three seconds.
Note:
The state of the EZ-Function Key (high or low) is maintained with each successive push of
the key.
Configuring a Digital Input to Start and Stop a Profile
1. Navigate to the Setup Page and then the Digital I/O menu. From the Home Page, press
and hold the ¿ or Down ¯ key for approximately six seconds where the upper display
will show ai and the lower display will show SEt.
2. Press the Up ¿ or Down ¯ key to navigate to the Digital I/O menu. Upper display will
show dio and the lower display will show SEt.
3. Press the Advance Key ‰ where the rst available digital instance will be displayed in the
upper display.
4. Press the Up ¿ or Down ¯ key to select the input of choice.
5. Press the Advance Key ‰ to select the direction (input or output). In this example, select
Dry Contact iCon.
6. Select the level (high or low) that will activate the function by pressing the Advance Key
‰ where the upper display will show high and the lower display will show LEv.
7. Press the Up ¿ or Down ¯ keys to select the level that will start the prole (high =
closed or low = open).
8. Press the Advance Key ‰ to select the function fn. In this example, select Prole Start /
Stop P.sts.
9. Press the Advance Key ‰ to select the function instance (Prole to start).
10. Return to the Home Page by pressing and holding the Innity Key ˆ for approximately
three seconds.
Starting a Profile from the Operations Page
1. Navigate to the Operations Page and then the Prole Status menu. From the Home Page,
press and hold the ¿ or Down ¯ key for approximately three seconds where the upper
display will show ai and the lower display will show opEr.
2. Press the Up ¿ or Down ¯ key to navigate to the Prole Status P.sta menu.