Installation en
Installation and operating instructions Wilo-Control EC/ECe-Booster 61
6.5.9 Pressure sensor connection
NOTICE
Do not apply external voltage!
An external voltage which is applied destroys the component.
Pressure detection is performed using an analogue pressure sensor (4–20mA).
Insert the connection cable laid by the customer through the threaded cable glands and
secure. Connect the wires to the terminal strip according to the connection diagram.
Use the terminal number shown in the connection overview in the cover.
4-20 mA
In
p
Fig.14: Connection overview symbol
NOTICE!Use shielded connection cables! Apply the shielding on one side!
NOTICE!Observe the correct polarity of the pressure sensor! Do not attach an active
pressure sensor.
6.5.10 Connection to the dry-running
(low water level) protection
NOTICE
Do not apply external voltage!
An external voltage which is applied destroys the component.
!
Fig.15: Connection overview symbol
The low water level (dry-running protection) can also be monitored using a float- or
pressure switch:
Contact open: dry running
Contact closed: no dry running
The terminals are fitted with a converter bridge at the factory.
Insert the connection cable laid by the customer through the threaded cable glands and
secure. Remove the converter bridge and connect the wires to the terminal strip ac-
cording to the connection diagram. Use the terminal number shown in the connection
overview in the cover.
6.5.11 “Extern OFF” connection: Remote
deactivation
NOTICE
Do not apply external voltage!
An external voltage which is applied destroys the component.
Fig.16: Connection overview symbol
Remote deactivation of all pumps can be performed using a separate switch:
Contact closed: pumps enabled
Contact open: all pumps deactivated– the display shows the “Extern OFF” symbol.
The terminals are fitted with a converter bridge at the factory.
NOTICE!Remote deactivation is prioritised. All pumps are deactivated regardless of
their actual pressure value. The pumps cannot be operated in manual mode!
Insert the connection cable laid by the customer through the threaded cable glands and
secure. Remove the converter bridge and connect the wires to the terminal strip ac-
cording to the connection diagram. Use the terminal number shown in the connection
overview in the cover.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Wilo Control EC-Booster and is the answer not in the manual?

Wilo Control EC-Booster Specifications

General IconGeneral
BrandWilo
ModelControl EC-Booster
CategoryController
LanguageEnglish

Related product manuals