en Commissioning
70 WILO SE 2019-07
Fig.31: Menu 5.11
Menu no. 5.11
Description Pressure sensor measurement range
Value range 1 … 25bar
Factory setting 16bar
Fig.32: Menu 5.14
Menu no. 5.14 (Control ECe-Booster only)
Description PID controller: Proportional factor
Value range 0.1 … 100
Factory setting 2.5
Explanation
Fig.33: Menu 5.15
Menu no. 5.15 (Control ECe-Booster only)
Description PID controller: Integral factor
Value range 0 … 300
Factory setting 0.5
Explanation
Fig.34: Menu 5.16
Menu no. 5.16 (Control ECe-Booster only)
Description PID controller: Differential factor
Value range 0 … 300
Factory setting 0
Explanation
Fig.35: Menu 5.40
Menu no. 5.40
Description Switch “pump kick” function On/Off
Value range off, on
Factory setting on
Fig.36: Menu 5.41
Menu no. 5.41
Description Allows “pump kick” when status is Extern OFF
Value range off, on
Factory setting on
Fig.37: Menu 5.42
Menu no. 5.42
Description “Pump kick” interval
Value range 1 … 336h
Factory setting 24h