7 Operations After Replacing Parts
FS100 7.1 Home Position Calibration
7-7
7.1.2.3 Changing the Absolute Data
To change the absolute data of the axis when home position calibration is
completed, perform the following:
1. Select {ROBOT} under the main menu.
2. Select {HOME POSITION}.
3. Select the desired control group.
– Perform steps 3 and 4 which have been described in "Registering All
Axes at One Time" to select the desired control group
4. Select the absolute data to be registered.
– The number can now be entered.
5. Enter the absolute data using the numeric keys.
6. Press [ENTER].
– Absolute data are modified.