6 DCP Interface
22 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum
0 : v 0.3 m/s
1 : v < 0.3 m/s
Bit S5 : Desired distance / Speed accepted
DCP3 and DCP4:
0 : During Emergency Stop or Stall Prevention
1 : The speed was accepted by the drive controller
Bit S6 : Mechanical Brake
DCP3 and DCP4:
Corresponds to the mechanical brake relay of the drive controller.
0 : Mechanical brake closed
1 : Mechanical brake open
Bit S7 : Error in last message received
DCP3 and DCP4:
This bit is set if the drive controller has detected a checksum error in the last message from the lift controller and
has therefore ignored it. In this situation, the lift controller repeats the telegram automatically.
Data Bytes
Process Data Communication Data Checksum
1 2 3 4 5 6
Status Byte
(S7 ... S0)
Data Byte 1 Data Byte 2 Communication Byte 1 Communication Byte 2 Checksum
The content of the two data bytes depends on the type of transmitted message. Three different kinds of
information can be transmitted:
Extended status of the drive controller
15-bit deceleration distance
16-bit deceleration distance
Extended status of the drive controller
Bit 0 : V
Unlock
Speed for Unlocking Zone
The actual speed is slower than the maximum speed for unlocking zone (v < 0.8 m/s).
0 : The actual speed is faster or equal than the max. speed for unlocking zone (v >= 0.8 m/s)
1 : The actual speed is slower than the max. speed for unlocking zone (v < 0.8 m/s)
Bit 1 : V
Border
Border Speed
The actual speed is slower than the adjustable border speed [d1-30].
0 : The actual speed is faster or equal than the border speed (v >= v
Border
)
1 : The actual speed is slower than the border speed (v < v
Border
)
Bit 2 : V
Over
Overspeed
The actual speed is slower than the adjustable overspeed [d1-31].
0 : The actual speed is faster or equal than the overspeed (v >= v
Over
)
1 : The actual speed is slower than the overspeed (v < v
Over
)
Bit 3 : Reserved
Currently not supported.
Bit 4 - 8 : Reserved for Weight Detection
Currently not supported.
Bit 9 : Emergency Power: Reduced DC Bus Voltage (Battery Supply/UPS)
The drive controller has reduced voltage (supplied by battery/UPS) during emergency power.
0 : Reduced DC Bus voltage not active
1 : Reduced DC bus voltage active

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA L1000A CIMR-LC F Series and is the answer not in the manual?

YASKAWA L1000A CIMR-LC F Series Specifications

General IconGeneral
Enclosure RatingIP20
Frequency Range50/60Hz
Protection FeaturesOvercurrent, Overvoltage, Undervoltage
Communication InterfaceModbus
Storage Temperature-20°C to +60°C (-4°F to +140°F)
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled

Related product manuals