6 DCP Interface
50 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum
Premature Termination of the 'Fast-Start Function'
There are some situations where it is necessary to abort the 'Fast-Start Function'. Examples for these situations
are:
The doors are reversing (opening again).
A time-out occurs (e.g. the doors can't be closed because they are blocked).
A fault occurs (e.g. motor thermistor or a leaving of the door zone).
In principle, there are two ways how the 'Fast-Start Function' can be aborted:
Immediate termination regardless of the state of the drive controller's status bit S6 'mechanical brake'.
Premature termination considering the state of the drive controller's status bit S6 'mechanical brake'.
Immediate Termination Regardless of S6 'Mechanical Brake' Status :
The 'Fast-Start Function' can be terminated immediately by clearing the lift controller's command byte.
Note:
A termination of the 'Fast-Start Function' regardless of the state of the drive controller's status bit S6 'mechanical brake' can cause a
drifting of the car and a disconnection of the main contactors under load. Therefore, whenever possible, termination considering the
state of the drive controller's status bit S6 'mechanical brake' should be preferred.