2 Brake Monitoring (Unintended Car Movement)
YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 9
Feedback function is just monitoring the brake operation and issues a fault if the brakes status does not match the
brake command.
Deactivation
To deactivate the Brake Response Monitor (BRM) function, perform the following steps:
Set S6-17 = 0.
The function is disabled.
Fault Detection/Fault Reset
Fault Detection
If during the start or stop process Brake Feedback 1 and/or Brake Feedback 2 do not change their logic state
within the time limit specified in S6-05 [Brake Response Error (SE4) Detection Time], an SE4 fault will be
triggered and the drive will be locked.
If during Run Brake Feedback 1 or Brake Feedback 2 change their logic state for a time longer than S6-06 [Brake
Response Error (SE4) Detection Time During Run], an SE4 fault will be triggered and the drive will be locked.
SE4 Fault Reset
With the Brake Response Monitor function enabled [S6-17 = 1], an SE4 fault cannot be reset by:
Using the Reset button
Power cycling the drive or installation
Using the Automatic Fault Reset function [L5-xx]
The SE4 fault can be reset only by setting parameter S6-18 = 1.
With the Brake Response Monitor (BRM) function disabled [S6-17 = 0], an SE4 fault can be reset using the
standard procedure.
Brake Feedback
Standard Behavior of Brake Feedback
After the Brake Release Command is set (brake open) during start procedure, the drive starts a timer with the
value set in parameter S6-05. If Brake Feedback function 79h is selected, both of the Brake Feedback Inputs must
be set within the time set in S6-05. If Brake Feedback function 5Bh is selected, they must be reset within the time
set in S6-05.
After the Brake Release Command is reset (brakes closed) during stop procedure, the drive starts a timer with the
value set in parameter S6-05. If Brake Feedback function 79h is selected, both of the Brake Feedback Inputs must
be set within the time set in S6-05. If Brake Feedback function 5Bh is selected, they must be reset within the time
set in S6-05.
EN

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA L1000A CIMR-LC F Series and is the answer not in the manual?

YASKAWA L1000A CIMR-LC F Series Specifications

General IconGeneral
Enclosure RatingIP20
Frequency Range50/60Hz
Protection FeaturesOvercurrent, Overvoltage, Undervoltage
Communication InterfaceModbus
Storage Temperature-20°C to +60°C (-4°F to +140°F)
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled

Related product manuals