12 Travel Direction Change Counter
86 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum
Note:
• If o4-40 is active and you have not set a password, a TCS alarm [TDCC Setup Alarm] is present.
• During maintenance, log the values for U4-64 to U4-68 and o4-41 occasionally.
If a drive brakes and cannot be powered on anymore, these values cannot be restored. In such a case, a person responsible for elevator
safety must decide if ropes need to be replaced or if values can be estimated.
◆ Counter Reset
To reset the Travel Direction Change Counter (TDCC) after you replaced ropes, enter the limit of bending
changes to TDCC Pres Value [o4-42]. The value entered is in thousands, e.g. when you enter ‘1’ it means 1000
direction changes are allowed.
When you entered the value, the monitors Rem Dir Chg [U4-65, U4-66] will be updated, and 04-42 will be reset
to 0.
◆ Related Parameters and Monitors
■ Added Parameters
Parameter Operator Display Content Value Range Default Value
o4-40 TDCC Enable
Travel Direction Change Counter Enable
Enables the TDCC function:
0 : Disabled
1 : Enabled
0, 1 0
o4-41 TDCC Alarm Level
Travel Direction Change Counter Alarm Level
Sets the Trip Counter Alarm level. The value is set in units of 1 kilo
(1000).
0k - 10000k 50k
o4-42 TDCC Pres Value
Travel Direction Change Counter Preset Value
Sets the number of allowable direction changes after a rope change. The
unit is kilo (1k = 1000). The direction counter [U4-66/U4-67] is set to the
input value and the parameter is changed back to 0.
0k - 65535k 0k
o4-43 TDCC Pswd Set
Travel Direction Change Counter Password Setting
Sets the Travel Direction Change Counter password. The password needs
to be entered twice (identically). The active password locks parameters o4-
40 to o4-43 from editing and starts the TDC counting process. The
password can only be set when o4-40 is enabled. When the same password
is entered again, the parameters are unlocked again. The password is not
displayed. A coded value is shown:
0 : Password not set
1 : Password set
2 : Password set and entered (unlocked)
3 - FFFF : Password
Only values 3 to FFFFh are accepted as password.
A set password is not reset by A1-03 initialization (including EEPROM
initialization 9990).
0 - FFFF 0
■ Added Monitors
Parameter
(Hex.)
Operator Display Content
Analog Output
Scaling
Range/Unit
U4-65
(830)
Rem Dir Chg L
Shows the lower three digits of actual TDCC value. It is reset to 0 after
1000 direction changes.
- 0 - 999
U4-66
(831)
Rem Dir Chg H Shows the remaining upper digits of actual TDCC value. - 0k - 65535k
U4-67
(832)
Total Dir Chg L
Shows the lower three digits of total TDCC value. It is reset to 0 after 1000
direction changes.
- 0 - 999
U4-68
(833)
Total Dir Chg H
Shows the remaining upper digits of total TDCC value (1 = 1000 = 1k).
The value saturates at 65535k.
- 0k - 65535k
U4-69
(834)
Total TDCC Pres
Shows the number of preset operations (includes reset to 0) of the TDCC.
The value saturates at 63. This is intended to uncover possible misuse.
- 0 - 63
U4-70
(835)
Last DirChg Pres
Shows the most recent value, input to o4-42 for resetting the remaining
direction changes counter.
- 0 - 65535k