12 Travel Direction Change Counter
86 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum
Note:
If o4-40 is active and you have not set a password, a TCS alarm [TDCC Setup Alarm] is present.
During maintenance, log the values for U4-64 to U4-68 and o4-41 occasionally.
If a drive brakes and cannot be powered on anymore, these values cannot be restored. In such a case, a person responsible for elevator
safety must decide if ropes need to be replaced or if values can be estimated.
Counter Reset
To reset the Travel Direction Change Counter (TDCC) after you replaced ropes, enter the limit of bending
changes to TDCC Pres Value [o4-42]. The value entered is in thousands, e.g. when you enter 1 it means 1000
direction changes are allowed.
When you entered the value, the monitors Rem Dir Chg [U4-65, U4-66] will be updated, and 04-42 will be reset
to 0.
Related Parameters and Monitors
Added Parameters
Parameter Operator Display Content Value Range Default Value
o4-40 TDCC Enable
Travel Direction Change Counter Enable
Enables the TDCC function:
0 : Disabled
1 : Enabled
0, 1 0
o4-41 TDCC Alarm Level
Travel Direction Change Counter Alarm Level
Sets the Trip Counter Alarm level. The value is set in units of 1 kilo
(1000).
0k - 10000k 50k
o4-42 TDCC Pres Value
Travel Direction Change Counter Preset Value
Sets the number of allowable direction changes after a rope change. The
unit is kilo (1k = 1000). The direction counter [U4-66/U4-67] is set to the
input value and the parameter is changed back to 0.
0k - 65535k 0k
o4-43 TDCC Pswd Set
Travel Direction Change Counter Password Setting
Sets the Travel Direction Change Counter password. The password needs
to be entered twice (identically). The active password locks parameters o4-
40 to o4-43 from editing and starts the TDC counting process. The
password can only be set when o4-40 is enabled. When the same password
is entered again, the parameters are unlocked again. The password is not
displayed. A coded value is shown:
0 : Password not set
1 : Password set
2 : Password set and entered (unlocked)
3 - FFFF : Password
Only values 3 to FFFFh are accepted as password.
A set password is not reset by A1-03 initialization (including EEPROM
initialization 9990).
0 - FFFF 0
Added Monitors
Parameter
(Hex.)
Operator Display Content
Analog Output
Scaling
Range/Unit
U4-65
(830)
Rem Dir Chg L
Shows the lower three digits of actual TDCC value. It is reset to 0 after
1000 direction changes.
- 0 - 999
U4-66
(831)
Rem Dir Chg H Shows the remaining upper digits of actual TDCC value. - 0k - 65535k
U4-67
(832)
Total Dir Chg L
Shows the lower three digits of total TDCC value. It is reset to 0 after 1000
direction changes.
- 0 - 999
U4-68
(833)
Total Dir Chg H
Shows the remaining upper digits of total TDCC value (1 = 1000 = 1k).
The value saturates at 65535k.
- 0k - 65535k
U4-69
(834)
Total TDCC Pres
Shows the number of preset operations (includes reset to 0) of the TDCC.
The value saturates at 63. This is intended to uncover possible misuse.
- 0 - 63
U4-70
(835)
Last DirChg Pres
Shows the most recent value, input to o4-42 for resetting the remaining
direction changes counter.
- 0 - 65535k

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA L1000A CIMR-LC F Series and is the answer not in the manual?

YASKAWA L1000A CIMR-LC F Series Specifications

General IconGeneral
Enclosure RatingIP20
Frequency Range50/60Hz
Protection FeaturesOvercurrent, Overvoltage, Undervoltage
Communication InterfaceModbus
Storage Temperature-20°C to +60°C (-4°F to +140°F)
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled

Related product manuals