1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 169
Parameter Details
1
Setting 1E: Restart Enabled
The Restart Enabled output will be closed once the fault restart function becomes active and
will remain closed until a successful restart is accomplished or the number of Auto Restart
attempts as specified by L5-01 is reached. Refer to L5: Fault Restart on page 209 for details
on automatic fault restart.
Setting 1F: Motor Overload Alarm oL1
An output programmed for this function will be closed when the motor overload level
estimated by the OL1 fault detection exceeds 90% of the OL1 detection level. Refer to L1-
01: Motor Overload Protection Function Selection on page 185 for details.
Setting 20: Drive Overheat Pre-alarm (OH)
Output closes whenever the drive heatsink temperature reaches the level specified by
parameter L8-02. Refer to L8-02: Overheat Alarm Level on page 217 for details on drive
overheat detection.
Setting 22: Mechanical Weakening Detection
Output closes when mechanical weakening is detected. Refer to Mechanical Weakening
Detection on page 214 for details.
Setting 30: During Torque Limit
Output closes when the motor is operating at the torque limit specified by the L7-
parameters or an analog input. This setting is only valid when using Open Loop Vector
Control (A1-02 = 2). Refer to L7-01/02/03/04: Torque Limits on page 216 for details.
Setting 37: During Frequency Output
Output closes when the drive is outputting a frequency.
Status Description
Open Motor 1 is selected.
Closed Motor 2 is selected.