INSPECTION, MAINTENANCE AND TROUBLESHOOTING
6.2.1 Troubleshooting Problems with Alarm Displaycont.
360
Display and Outputs
Digital Operator
Alarm Output
Display and
Alarm Code Output
Alarm Output
arm
ame
ALO1 ALO2 ALO3
A.b1
Reference input
read error (for
speed/torque
control only)
OFF OFF OFF OFF
OFF: Output transistor is OFF
ON: Output transistor is ON
Status When Alarm Occurred
A
,
B
During servomotor
operation
At power ON
C
Cause Remedy
A Part malfunctioned in reference read-in unit
(A/D converter, etc.).
Reset alarm and restart operation.
B Part defective in reference read-in unit
(A/D converter, etc.).
Replace Servopack.
C Circuit board (1PWB) defective Replace Servopack.
Display and Outputs
Digital Operator
Alarm Output
Display and
Alarm Code Output
Alarm Output
arm
ame
ALO1 ALO2 ALO3
A.C1
Servo overrun
ON OFF ON OFF
OFF: Output transistor is OFF
ON: Output transistor is ON
Status When Alarm Occurred
E
At power ON
User constant
Cn-01 Bit 0 = 0
When servo ON (S-ON)
signal turned ON
A
,
B
,C,D,E
On speed reference input
A
,
B
,C,D,E
A
,
B
,C,D,E
Occurred 1 to 3 se-
conds after power ON
User constant
Cn-01 Bit 0 = 1
6