<66> Start /pick-up L
3
<67> Start /pick-up N
<68> General trip
<69> Trip L
1
<70> Trip L
2
<71> Trip L
3
<72> Trip I>> (back-up operation)
<73> Fault location X in ohms
<74> Fault forward/line
<75> Fault reverse/busbar
<76> Teleprotection signal transmitted
<77> Teleprotection signal received
<78> Zone 1
<79> Zone 2
<80> Zone 3
<81> Zone 4
<82> Zone 5
<83> Zone 6
<84> General start/pick-up
<85> Breaker failure
<86> Trip measuring system L
1
<87> Trip measuring system L
2
<88> Trip measuring system L
3
<89> Trip measuring system E
<90> Trip I>
<91> Trip I>>
<92> Trip IN>
<93> Trip IN>>
Note: In this IED series, function-specific fault signals are as default mapped to private data locations.
3.3.3.6 Auto-reclosure indications in monitor direction
INF Semantics
<128> CB ’on’ by AR
<129> CB ’on’ by long-time AR
<130> AR blocked
Note <129>: Terms 'short-' or 'long-time' AR are not directly usable in this IED series. The AR
functionality in the IED performs AR shots (1..5) that are user configurable. See private AR data
definitions. Depending on user AR configuration it is possible to re-map some private data into
standard data, if wanted.
Section 3 1MRS757657 A
Interoperability profile for 620 series IEC 60870-5-103
58 REM620
Point List Manual