3.3.3.7 Measurands in monitor direction
INF Semantics
<144> Measurand I
<145> Measurands I, V
<146> Measurands I, V, P, Q
<147> Measurands I
N
, V
EN
<148> Measurands I
L1,2,3
, V
L1,2,3
, P, Q, f
3.3.3.8 Generic functions in monitor direction
INF Semantics
<240> Read headings of all defined groups
<241> Read values or attributes of all entries of one group
<243> Read directory of a single entry
<244> Read value or attribute of a single entry
<245> End of general interrogation of generic data
<249> Write entry with confirmation
<250> Write entry with execution
<251> Write entry aborted
3.3.4 Selection of standard information numbers in control
direction
3.3.4.1 System functions in control direction
INF Semantics
<0> Initiation of general interrogation
<0> Time synchronization
3.3.4.2 Generic functions in monitor direction
INF Semantics
<240> Read headings of all defined groups
<241> Read values or attributes of all entries of one group
<243> Read directory of a single entry
<244> Read value or attribute of a single entry
<245> End of general interrogation of generic data
<249> Write entry with confirmation
<250> Write entry with execution
<251> Write entry aborted
1MRS757657 A Section 3