174 Parameters
06.39 Internal state
machine LSU CW
(Only visible when supply unit control activated by 95.20)
Shows the control word sent to the supply unit from the INU-
LSU (inverter unit/supply unit) state machine.
This parameter is read-only.
-
0000h…FFFFh Supply unit control word. 1 = 1
06.40 LSU CW user bit 0
selection
(Only visible when supply unit control activated by 95.20)
Selects a binary source whose status is transmitted as bit 12
of 06.39 Internal state machine LSU CW to the supply unit.
MCW user bit
0
False 0. 0
True 1. 1
MCW user bit 0 Bit 12 of 06.01 Main control word (see page 165). 2
MCW user bit 1 Bit 13 of 06.01 Main control word (see page 165). 3
MCW user bit 2 Bit 14 of 06.01 Main control word (see page 165). 4
MCW user bit 3 Bit 15 of 06.01 Main control word (see page 165). 5
Other [bit] Source selection (see Terms and abbreviations on page 148). -
06.41 LSU CW user bit 1
selection
(Only visible when supply unit control activated by 95.20)
Selects a binary source whose status is transmitted as bit 13
of 06.39 Internal state machine LSU CW to the supply unit.
MCW user bit
1
False 0. 0
True 1. 1
MCW user bit 0 Bit 12 of 06.01 Main control word (see page 165). 2
MCW user bit 1 Bit 13 of 06.01 Main control word (see page 165). 3
MCW user bit 2 Bit 14 of 06.01 Main control word (see page 165). 4
MCW user bit 3 Bit 15 of 06.01 Main control word (see page 165). 5
Other [bit]
Source selection (see Terms and abbreviations on page 148). -
06.42 LSU CW user bit 2
selection
(Only visible when supply unit control activated by 95.20)
Selects a binary source whose status is transmitted as bit 14
of 06.39 Internal state machine LSU CW to the supply unit.
MCW user bit
2
False 0. 0
True 1. 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 ON/OFF 1 = Start charging
0 = Open main contactor (switch power off)
1 OFF 2 0 = Emergency stop (Off2)
2 OFF 3 0 = Emergency stop (Off3)
3 START 1 = Start modulating
0 = Stop modulating
4…6 Reserved
7 RESET 0
-
> 1 = Reset an active fault. A fresh start command is required after reset.
8…11 Reserved
12 USER BIT 0 See parameter 06.40 LSU CW user bit 0 selection.
13 USER BIT 1 See parameter 06.41 LSU CW user bit 1 selection.
14 USER BIT 2 See parameter 06.42 LSU CW user bit 2 selection.
15 USER BIT 3 See parameter 06.43 LSU CW user bit 3 selection.