14.35 RO1 ON delay (Visible when 14.01 Module 1 type = FIO-01 or FDIO-01)
Defines the activation delay for relay output RO1.
0.00 s
t
On
= 14.35 RO1 ON delay
t
Off
= 14.36 RO1 OFF delay
0.00 3000.00 s Activation delay for RO1. 10 = 1 s
14.35 AI1 scaled at AI1
min
(Visible when 14.01 Module 1 type = FIO-11 or FA IO-0 1)
Defines the real value that corresponds to the minimum
analog input AI1 value defined by parameter 14.33 AI1 min.
0.000
-32768.000 …
32767.000
Real value corresponding to minimum AI1 value. 1 = 1
14.36 RO1 OFF delay (Visible when 14.01 Module 1 type = FIO-01 or FDIO-01)
Defines the deactivation delay for relay output RO1. See
parameter 14.35 RO1 ON delay.
0.00 s
0.00 3000.00 s Deactivation delay for RO1. 10 = 1 s
14.36 AI1 scaled at AI1
max
(Visible when 14.01 Module 1 type = FIO-11 or FA IO-0 1)
Defines the real value that corresponds to the maximum
analog input AI1 value defined by parameter 14.34 AI1 max.
See the drawing at parameter 14.35 AI1 scaled at AI1 min.
100.000
-32768.000 …
32767.000
Real value corresponding to maximum AI1 value. 1 = 1
14.37 RO2 source (Visible when 14.01 Module 1 type = FIO-01 or FDIO-01)
Selects a drive signal to be connected to relay output RO2.
For the available selections, see parameter 14.11 DIO1
output source.
Not
energized
No. Name/Value Description Def/FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
RO status
Time
14.36
14.34
14.33
14.35
AI
in
(14.26)
AI
scaled
(14.27)