396 Parameters
Frequency 01.06 Output frequency is sent as actual value 1. The scaling
is defined by parameter 46.02 Frequency scaling.
5
60.13 M/F act2 type Selects the type/source and scaling of actual value ACT2
transmitted to the master/follower link.
Auto
Auto Type/source and scaling follow the type of reference 2
selected by parameter 60.11 M/F ref2 type. See the individual
settings below for the sources and scalings.
0
Transparent Reserved. 1
General Reserved. 2
Torque 01.10 Motor torque is sent as actual value 2. The scaling is
defined by parameter 46.03 Torque scaling.
3
Speed 01.01 Motor speed used is sent as actual value 2. The scaling
is defined by parameter 46.01 Speed scaling.
4
Frequency 01.06 Output frequency is sent as actual value 2. The scaling
is defined by parameter 46.02 Frequency scaling.
5
60.14 M/F follower
selection
(Effective in the master only.) Defines the followers from
which data is read. See also parameters 62.2862.33.
None
Follower node 2 Data is read from the follower with node address 2. 2
Follower node 3 Data is read from the follower with node address 3. 4
Follower node 4 Data is read from the follower with node address 4. 8
Follower nodes 2+3 Data is read from the followers with node addresses 2 and 3. 6
Follower nodes 2+4 Data is read from the followers with node addresses 2 and 4. 10
Follower nodes 3+4 Data is read from the followers with node addresses 3 and 4. 12
Follower nodes
2+3+4
Data is read from the followers with node addresses 2, 3 and
4.
14
None None. 0
60.15 Force master When parameter 60.03 M/F mode is set to DDCS forcing or
D2D forcing, this parameter selects a source that forces the
drive to be the master on the master/follower link.
1 = Drive is master on the master/follower link
FALS E
FALSE 0. 0
TRUE 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 148). -
60.16 Force follower When parameter 60.03 M/F mode is set to DDCS forcing or
D2D forcing, this parameter selects a source that forces the
drive to be a follower on the master/follower link.
1 = Drive is follower on the master/follower link
FALS E
FALSE 0. 0
TRUE 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 148). -
No. Name/Value Description Def/FbEq16