current is set by parameter 21.10. When the reference exceeds parameter 21.9,
normal drive operation continues.
Motor speed
Reference
21.09
DC hold
t
t
Note:
DC hold is only available in speed control in DTC motor control mode (see page
42).
The function applies the DC current to one phase only, depending on the
position of the rotor. The return current will be shared between the other
phases.
Post-magnetization
This feature keeps the motor magnetized for a certain period (parameter 21.11)
after stopping. This is to prevent the machinery from moving under load, for
example before a mechanical brake can be applied. Postmagnetization is activated
by parameter 21.8. The magnetization current and time are set by parameters 21.10
and 21.11.
Note: Post-magnetization is only available when ramping is the selected stop
mode (see parameter 21.3).
Continuous magnetization
A digital signal, such as a user bit in the fieldbus control word, can be selected to
activate continuous magnetization. This can be especially useful in processes
Program features 107