ABB ACS880 - O Bus Diagnostics

ABB ACS880
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Distributed I/O bus settings.I/O bus
diagnostics
208
This group is only visible with a BCU control unit.
This group contain parameters related to the
distributed I/O bus, which is used with some drives for
monitoring the cooling fans of the cabinet system. For
details, refer to
CIO-01 I/O module for distributed I/O
bus control user’s manual
(3AXD50000126880
[English]).
- / uint32Displays a count of messages (ie. packets) transmitted
by the master.
Transmitted packets208.1
1 / 1Number of messages transmitted by the master.0...2147483647
- / uint32Displays a count of messages (ie. packets) sent to the
master.
Received packets208.2
1 / 1Number of messages received by the master.0...2147483647
- / uint32Displays a count of packets with a CRC error. An
increasing count indicates errors in the check sum.
CRC errors208.3
1 / 1Number of CRC errors.0...2147483647
- / uint32Displays a count of character errors. An increasing
count indicates a configuration problem on the bus.
UART errors208.4
1 / 1Number of UART errors.0...2147483647
- / uint32Displays a count of Modbus® errors. An increasing
count indicates errors on the Modbus protocol.
Modbus errors208.5
1 / 1Number of Modbus errors.0...2147483647
- / uint32Displays a sum of time outs in all of the nodes (see
parameters 208.11…208.26). A time out is a request
Timeouts208.6
response cycle in the I/O bus, where the bus master
sends a request but does not get a correctly-formed
response message in return within the time window
reserved for the cycle.
1 / 1Number of timeouts.0...2147483647
- / uint32Displays a count of timeouts in node 1.Node 1 timeouts208.11
1 / 1Number of timeouts in node 1.0...2147483647
- / uint32Displays a count of timeouts in node 2.Node 2 timeouts208.12
1 / 1Number of timeouts in node 2.0...2147483647
- / uint32Displays a count of timeouts in node 3.Node 3 timeouts208.13
1 / 1Number of timeouts in node 3.0...2147483647
- / uint32Displays a count of timeouts in node 4.Node 4 timeouts208.14
1 / 1Number of timeouts in node 4.0...2147483647
- / uint32Displays a count of timeouts in node 5.Node 5 timeouts208.15
1 / 1Number of timeouts in node 5.0...2147483647
- / uint32Displays a count of timeouts in node 6.Node 6 timeouts208.16
1 / 1Number of timeouts in node 6.0...2147483647
- / uint32Displays a count of timeouts in node 7.Node 7 timeouts208.17
642 Parameters