The number of digital inputs/outputs can be increased by installing FIO-01, FIO-11
or FDIO-01 I/O extensions (see Programmable I/O extensions below). The digital
inputs on extension modules are read on a 2 ms time level.
Settings and diagnostics
Parameter groups: 10 Standard DI, RO (page 211) and 11 Standard DIO, FI,
FO (page 218).
Events: -
Programmable frequency input and output
Digital input DI5 can be used as a frequency input.
Settings and diagnostics
Parameter groups: 10 Standard DI, RO (page 211) and
11 Standard DIO, FI, FO
.
Events: -
Programmable relay outputs
The control unit has three relay outputs. The signal to be indicated by the outputs
can be selected by parameters.
The relay outputs on the control unit are updated on a 0.5 ms time level.
Relay outputs can be added by installing FIO-01 or FDIO-01 I/O extensions. The
relay outputs on extension modules are updated on a 2 ms time level.
Settings and diagnostics
Parameter groups: 10 Standard DI, RO (page 211)
Events: -
Programmable I/O extensions
Inputs and outputs can be added by using I/O extension modules. One to three
modules can be mounted on the slots of the control unit. Slots can be added by
connecting an FEA-03 I/O extension adapter.
The table below shows the number of I/O on the control unit as well as optional
I/O extension modules.
Relay outputs
(RO)
Analog out-
puts (AO)
Analog inputs
(AI)
Digital I/Os
(DIO)
Digital inputs
(DI)
Location
32226 + DIILControl unit
2--4-FIO-01
-132-FIO-11
-22--FAIO-01
Program features 71