EasyManua.ls Logo

ABB ACS880 - H Pump Curves

ABB ACS880
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Estimates flowrate of pump curves in ESP application.Q-H pump curves85
See section
Pump curves
.
Input 1 - Input 2 /
unit32
Selects the method for the pump curve input
processing.
The user has two source parameters for the pump curve
input (85.02 Input 1 source and 85.03 Input 2 source).
Pump curve input
function
85.01
The used input for the pump curve function could be
either of source parameters or result of math operation
between the two.
-ZeroNULL
-Parameter 85.02 Input 1 source is input for pump curves
function.
Input 1 Direct
-Parameter 85.03 Input 2 source is input for pump curves
function.
Input 2 Direct
-Sum of 85.02 Input 1 source and 85.03 Input 2 source
is the input of pump curves function.
Input 1 + Input 2
-Difference of 85.02 Input 1 source and 85.03 Input 2
source is the input of pump.
Input 1 - Input 2
-Multiply of 85.02 Input 1 source and 85.03 Input 2 source
is the input of pump curves function.
Input 1 × Input 2
-Division of 85.02 Input 1 source and 85.03 Input 2 source
is the input of pump curves function.
Input 1 / Input 2
See Terms and abbreviations (page 169).Other [value]
Aux input data 1 /
unit32
Defines source 1 for signal that can be used as an input
for the pump curve function.
Input 1 source85.02
0ZeroNULL
112.12 AI1 scaled value (page 226).AI1 scaled
212.22 AI2 scaled value (page 228).AI2 scaled
33.5 FB A reference 1 (page 179).FBA1 ref
43.6 FB A reference 2 (page 179).FBA2 ref
53.9 EFB reference 1 (page 179).EFB1 ref
63.10 EFB reference 2 (page 179).EFB2 ref
7Value set in parameter 85.71 Aux input data 1.Aux input data 1
8Value set in parameter 85.72 Aux input data 2.Aux input data 2
See Terms and abbreviations (page 169).Other [value]
Aux input data 2 /
unit32
Defines source 2 for signal that can be used as an input
for the pump curve function.
For parameter selections, see parameter 85.02 Input 1
source.
Input 2 source85.03
0.00 Hz / real32Defines Q-H pump curve frequency 1.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
Curve frequency 185.04
10 = 1 Hz / 100 = 1 HzCurve frequency in Hz.0.00 ... 600.00 Hz
Parameters 559