Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / real32Displays the value of analog input AI2 after scaling. See
parameters 12.29 AI2 scaled at AI2 min and 12.30 AI2
scaled at AI2 max.
This parameter is read-only.
AI2 scaled value12.22
1 = 1 / 1000 = 1Scaled value of analog input AI2.-32768.000 ...
32767.000
mA / uint16Selects the unit for readings and settings related to
analog input AI2.
Note: This setting must match the corresponding
hardware setting on the drive control unit (see the
hardware manual of the drive). Control board reboot
(either by cycling the power or through parameter 96.8
Control board boot) is required to validate any changes
in the hardware settings.
AI2 unit selection12.25
2Volts.V
10Milliamperes.mA
0.100 s / real32Defines the filter time constant for analog input AI2.
See parameter 12.16 AI1 filter time.
AI2 filter time12.26
1000 = 1 s / 1000 = 1
s
Filter time constant.0.000 ... 30.000 s
0.000 mA or V /
real32
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog
signal from plant is wound to its minimum setting.
See also parameter 12.1 AI tune.
AI2 min12.27
1000 = 1 mA or V /
1000 = 1 mA or V
Minimum value of AI2.-22.000 ... 22.000 mA
or V
20.000 mA or V /
real32
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog
signal from plant is wound to its maximum setting.
See also parameter 12.1 AI tune.
AI2 max12.28
1000 = 1 mA or V /
1000 = 1 mA or V
Maximum value of AI2.-22.000 ... 22.000 mA
or V
228 Parameters