selection between external control locations 1/2, or fault reset). The drive switches
between its states according to the bit-coded instructions of the CW.
The fieldbus CW is either written to the drive as it is (see parameter 6.5 EFB
transparent control word), or the data is converted. See section About the control
profiles (page 713).
The fieldbus Status Word (SW) is a 16-bit or 32-bit packed boolean word. It contains
status information from the drive to the fieldbus controller. The drive SW is either
written to the fieldbus SW as it is or the data is converted. See section About the
control profiles (page 713).
References
EFB references 1 and 2 are 16-bit or 32-bit signed integers. The contents of each
reference word can be used as the source of virtually any signal, such as the speed,
frequency, torque or process reference. In embedded fieldbus communication,
references 1 and 2 are displayed by 3.9 EFB reference 1 and 3.10 EFB reference 2
respectively. Whether the references are scaled or not depends on the settings of
58.26 EFB ref1 type and 58.27 EFB ref2 type. See section About the control
profiles (page 713).
Actual values
Fieldbus actual signals (ACT1 and ACT2) are 16-bit or 32-bit signed integers. They
convey selected drive parameter values from the drive to the master. Whether the
actual values are scaled or not depends on the settings of 58.28 EFB act1 type and
58.29 EFB act2 type. See section About the control profiles (page 713).
Data input/outputs
Data input/outputs are 16-bit or 32-bit words containing selected drive parameter
values. Parameters 58.101 Data I/O 1 58.124 Data I/O 24 define the addresses
from which the master either reads data (input) or to which it writes data (output).
Control of drive outputs through EFB
The address selection parameters of the data input/outputs have a setting with
which the data can be written into a storage parameter in the drive. These storage
parameters are readily selectable as signal sources of the drive outputs.
The desired values of the relay outputs (RO) and digital input/outputs (DIO) can
be written in a 16-bit word into 10.99 RO/DIO control word, which is then selected
as the source of those outputs. Each of the analog outputs (AO) of the drive have
a dedicated storage parameter (13.91 AO1 data storage and 13.92 AO2 data storage),
which are available in the source selection parameters 13.12 AO1 source and 13.22
AO2 source.
712 Fieldbus control through the embedded fieldbus interface (EFB)