Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.000 mA or V /
real32
Defines the minimum site value for analog input AI1.
Set the value actually sent to the drive when the analog
signal from plant is wound to its minimum setting.
See also parameter 12.1 AI tune.
AI1 min12.17
1000 = 1 mA or V /
1000 = 1 mA or V
Minimum value of AI1.-22.000 ... 22.000 mA
or V
20.000 mA or V /
real32
Defines the maximum site value for analog input AI1.
Set the value actually sent to the drive when the analog
signal from plant is wound to its maximum setting.
See also parameter 12.1 AI tune.
AI1 max12.18
1000 = 1 mA or V /
1000 = 1 mA or V
Maximum value of AI1.-22.000 ... 22.000 mA
or V
0.000 / real32Defines the real internal value that corresponds to the
minimum analog input AI1 value defined by parameter
12.17 AI1 min. (Changing the polarity settings of 12.19
and 12.20 can effectively invert the analog input.)
AI
scaled
(
12.12
)
AI
in
(
12.11
)
12.20
12.17
12.18
12.19
AI1 scaled at AI1 min12.19
1 = 1 / 1000 = 1Real value corresponding to minimum AI1 value.-32768.000 ...
32767.000
1500.000; 1800.000
(95.20 b0) / real32
Defines the real internal value that corresponds to the
maximum analog input AI1 value defined by parameter
12.18 AI1 max. See the drawing at parameter 12.19 AI1
scaled at AI1 min.
AI1 scaled at AI1 max12.20
1 = 1 / 1000 = 1Real value corresponding to maximum AI1 value.-32768.000 ...
32767.000
- / real32Displays the value of analog input AI2 in mA or V
(depending on whether the input is set to current or
voltage by a hardware setting).
This parameter is read-only
AI2 actual value12.21
1000 = 1 mA or V /
1000 = 1 mA or V
Value of analog input AI2.-22.000 ... 22.000 mA
or V
Parameters 227