Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / real32Displays the value of analog input AI1 in mA or V
(depending on whether the input is set to current or
voltage by a hardware setting).
This parameter is read-only.
AI1 actual value12.11
1000 = 1 mA or V /
1000 = 1 mA or V
Value of analog input AI1.-22.000 ... 22.000 mA
or V
- / real32Displays the value of analog input AI1 after scaling. See
parameters 12.19 AI1 scaled at AI1 min and 12.20 AI1
scaled at AI1 max.
This parameter is read-only.
AI1 scaled value12.12
1 = 1 / 1000 = 1Scaled value of analog input AI1.-32768.000 ...
32767.000
V / uint16Selects the unit for readings and settings related to
analog input AI1.
Note: This setting must match the corresponding
hardware setting on the drive control unit (see the
hardware manual of the drive). Control board reboot
(either by cycling the power or through parameter 96.8
Control board boot) is required to validate any changes
in the hardware settings.
AI1 unit selection12.15
2Volts.V
10Milliamperes.mA
0.100 s / real32Defines the filter time constant for analog input AI1.
Unfiltered signal
Filtered signal
%
t
100
63
T
O = I × (1 - e
-
t
/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Note: The signal is also filtered due to the signal
interface hardware (approximately 0.25 ms time
constant). This cannot be changed by any parameter.
AI1 filter time12.16
1000 = 1 s / 1000 = 1
s
Filter time constant.0.000 ... 30.000 s
226 Parameters