Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = 1 % / 10 = 1 %Underload point.0.0 ... 1600.0 %
15.0 % / real32Defines the 2nd point of the underload curve.ULC underload point
2
37.22
1 = 1 % / 10 = 1 %Underload point.0.0 ... 1600.0 %
25.0 % / real32Defines the 3rd point of the underload curve.ULC underload point
3
37.23
1 = 1 % / 10 = 1 %Underload point.0.0 ... 1600.0 %
30.0 % / real32Defines the 4th point of the underload curve.ULC underload point
4
37.24
1 = 1 % / 10 = 1 %Underload point.0.0 ... 1600.0 %
30.0 % / real32Defines the 5th point of the underload curve.ULC underload point
5
37.25
1 = 1 % / 10 = 1 %Underload point.0.0 ... 1600.0 %
300.0 % / real32Defines the 1st point of the overload curve.
Each point of the overload curve must have a higher
value than the corresponding underload point.
ULC overload point
1
37.31
1 = 1 % / 10 = 1 %Overload point.0.0 ... 1600.0 %
300.0 % / real32Defines the 2nd point of the overload curve.ULC overload point
2
37.32
1 = 1 % / 10 = 1 %Overload point.0.0 ... 1600.0 %
300.0 % / real32Defines the 3rd point of the overload curve.ULC overload point
3
37.33
1 = 1 % / 10 = 1 %Overload point.0.0 ... 1600.0 %
300.0 % / real32Defines the 4th point of the overload curve.ULC overload point
4
37.34
1 = 1 % / 10 = 1 %Overload point.0.0 ... 1600.0 %
300.0 % / real32Defines the 5th point of the overload curve.ULC overload point
5
37.35
1 = 1 % / 10 = 1 %Overload point.0.0 ... 1600.0 %
20.0 s / real32Defines the time for which the monitored signal must
continuously stay above the overload curve before the
drive takes the action selected by 37.3 ULC overload
actions.
ULC overload timer37.41
1 = 1 s / 10 = 1 sOverload timer.0.0 ... 10000.0 s
20.0 s / real32Defines the time for which the monitored signal must
continuously stay below the underload curve before
the drive takes the action selected by 37.4 ULC
underload actions.
ULC underload timer37.42
1 = 1 s / 10 = 1 sUnderload timer.0.0 ... 10000.0 s
Parameters 419