Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
63.10 EFB reference 2 (page 179).EFB ref2
See Terms and abbreviations (page 169).Other [value]
Not selected / unit32Defines the source for custom u/f curve base.Custom u/f curve
base en
80.35
00.Not selected
11.Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
400.0 V / real32Defines base voltage set point.Base voltage set
point
80.36
1 = 1 V / 10 = 1 VBase voltage set point.0.0 ... 32767.0 V
50.00 Hz / real32Defines base frequency set point.Base frequency set
point
80.37
1 = 1 Hz / 100 = 1 HzBase frequency set point.0.00 ... 598.00 Hz
ESP CW bit 11 / real32Defines the source for the IR compensation enable
signal.
IR compensation
enable
80.40
0Validate tuning command is not selected.Not selected
1Validate tuning command is selected.Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
12Parameter 74.1 ESP control word (page 519), bit 11 status
controls enable/disable status of the function.
ESP CW bit 11
See Terms and abbreviations (page 169).Other [bit]