Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.0 A / real32Defines the nominal motor current. This setting must
match the value on the rating plate of the motor. If
multiple motors are connected to the drive, enter the
total current of the motors.
Note: Correct motor operation requires that the
magnetizing current of the motor does not exceed 90%
of the nominal current of the drive.
Note: This parameter cannot be changed while the
drive is running.
Motor nominal
current
99.6
1 = 1 A / 10 = 1 ANominal current of the motor. The allowable range is
1/6…2 ×
I
N
(nominal current) of the drive and 0…2 ×
I
N
with scalar control mode.
For ESP application, the recommended range is
1/3...2 ×
I
N
(nominal current) of the drive.
0.0 ... 6400.0 A
0.0 V / real32Defines the nominal motor voltage supplied to the
motor. This setting must match the value on the rating
plate of the motor.
Note: With permanent magnet motors the nominal
voltage is the motor nominal total voltage scaled to
low voltage side.
Note: The stress on the motor insulation is always
dependent on the drive supply voltage. This also applies
to the case where the motor voltage rating is lower
than that of the drive and the supply.
Note: This parameter cannot be changed while the
drive is running.
Motor nominal
voltage
99.7
10 = 1 V / 10 = 1 VNominal voltage of the motor. The allowable range is
1/6…2 ×
U
N
(nominal voltage) of the drive.
U
N
equals
the upper bound of the supply voltage range selected
by parameter 95.1 Supply voltage.
0.0 ... 800.0 V
50.00 Hz / real32Defines the nominal motor frequency. This setting must
match the value on the rating plate of the motor.
Note: This parameter cannot be changed while the
drive is running.
Motor nominal
frequency
99.8
10 = 1 Hz / 100 = 1 HzNominal frequency of the motor.0.00 ... 1000.00 Hz
0 rpm / real32Defines the nominal motor speed. The setting must
match the value on the rating plate of the motor.
Note: This parameter cannot be changed while the
drive is running.
Note: (Asynchronous generator) Nominal speed needs
to be adjusted as running the generator as a motor.
Motor nominal
speed
99.9
1 = 1 rpm / 1 = 1 rpmNominal speed of the motor.0...30000 rpm
622 Parameters