What to doCause
Event name /
Aux. code
Code
(hex)
Contact your local ABB
representative.
Failed answer to adapter
configuration message.
0004
Contact your local ABB
representative.
Too many failed answers inline to
speed and position messages.
0005
Contact your local ABB
representative.
DDCS driver failed.0006
Check the auxiliary code (format XXYY
YYYY). “XX” specifies the number of
The I/O extension module types
specified by parameters do not match
the detected configuration.
Ext I/O comm
loss
A799
the I/O extension module (01:
parameter group 14 I/O extension
module 1, 02: 15 I/O extension module
2 2, 03: 16 I/O extension module 3).
“YY YYYY” indicates the problem (see
actions for each code below).
Check that the module is properly
seated in its slot.
Communication with module failed.00 0001
Check that the module and the slot
connector is not damaged.
Try installing the module into
another slot.
Check the type and location settings
of the modules (parameters
14.1/14.2, 15.1/15.2 or 16.1/16.2).
Module not found.00 0002
Check that the module is properly
seated in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into
another slot.
Check the type and location settings
of the modules (parameters
14.1/14.2, 15.1/15.2 or 16.1/16.2).
Configuration of module failed.00 0003
Check that the module is properly
seated in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into
another slot.
Check the type and location settings
of the modules (parameters
14.1/14.2, 15.1/15.2 or 16.1/16.2).
Configuration of module failed.00 0004
Check that the module is properly
seated in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into
another slot.
Replace brake chopper if external.
Drives with internal choppers will need
to be returned to ABB.
Short circuit in brake chopper IGBT.BC short
circuit
A79B
Ensure brake resistor is connected and
not damaged.
682 Fault tracing