Parameters and firmware blocks
103
Group 10 START/STOP
Settings for
selecting start/stop/direction signal sources for external control locations EXT1
and EXT2
selecting sources for external fault reset, run enable and start enable signals
selecting sources for emergency stop (OFF1 and OFF3)
selecting source for jogging function activation signal
enabling the start inhibit function.
See also section Jogging on page 46.
10
10 START/STOP
Firmware block:
DRIVE LOGIC
(10)
This block
selects the sources for the start/
stop/direction signals for external
control locations EXT1 and EXT2
selects the sources for external
fault reset, run enable and start
enable signals
selects the sources for emergency
stop (OFF1 and OFF3)
selects the source for jogging
activation signal
enables the start inhibit function.
DRIVE LOGIC
21
TLF10 2 msec (3)
10.01 EXT1 START FUNC
[ In1 ]
< 10.02 EXT1 START IN1
[ DI STATUS.0 ]
(2 / 2.01.DI1)
< 10.03 EXT1 START IN2
[ FALSE ]
10.04 EXT2 START FUNC
[ In1 ]
< 10.05 EXT2 START IN1
[ DI STATUS.0 ]
(2 / 2.01.DI1)
< 10.06 EXT2 START IN2
[ FALSE ]
< 10.07 JOG1 START
[ FALSE ]
< 10.08 FAULT RESET SEL
[ DI STATUS.2 ]
(2 / 2.01.DI3)
< 10.09 RUN ENABLE
[ TRUE ]
< 10.10 EM STOP OFF3
[ TRUE ]
< 10.11 EM STOP OFF1
[ TRUE ]
10.12 START INHIBIT
[ Disabled ]
< 10.13 FB CW USED
[ FBA MAIN CW ]
(4 / 2.12)
< 10.14 JOG2 START
[ FALSE ]
< 10.15 JOG ENABLE
[ FALSE ]
< 10.16 D2D CW USED
[ D2D M AIN CW ]
(4 / 2.17)
< 10.17 START ENABLE
[ TRUE ]
2.18 D2D FOLLOWER CW
6.01 STATUS WORD 1
6.02 STATUS WORD 2
6.03 SPEED CTRL STAT
6.05 LIMIT WORD 1
6.07 TORQ LIM STATUS
6.09 POS CTRL STATUS
6.10 POS CTRL STATUS2
6.11 POS CORR STATUS