Standard function blocks
332
FIO_11_AI_slot2
(10089)
Illustration
Execution time 11.1 µs
Operation The block controls the three analogue inputs (AI1…AI3) of a FIO-11 Analog I/O
Extension mounted on slot 2 of the drive control unit.
The block outputs both the unscaled (AIx) and scaled (AIx scaled) actual values of each
analogue input. The scaling is based on the relationship between the ranges
AIx min … AIx max and AIx min scale … AIx max scale.
AIx Min must be smaller than AIx Max; AIx Max Scale can be greater or smaller than AIx
Min Scale.
FIO_11_AI_slot2
52
TLA1 1 msec (1)
AI1 filt gain
AI1 Min
AI1 Ma x
AI1 Min sc ale
AI1 Ma x scale
AI2 filt gain
AI2 Min
AI2 Ma x
AI2 Min sc ale
AI2 Ma x scale
AI3 filt gain
AI3 Min
AI3 Ma x
AI3 Min sc ale
AI3 Ma x scale
AI1 mode
AI1 mode(52)
AI1
AI1(52)
AI1 sca led
AI1 sca led(52)
AI2 mode
AI2 mode(52)
AI2
AI2(52)
AI2 sca led
AI2 sca led(52)
AI3 mode
AI3 mode(52)
AI3
AI3(52)
AI3 sca led
AI3 sca led(52)
Error
Error(52)
AIx scaled
32768
AIx [V or mA]
11 V or
-11 V or
AIx Max
AIx Min
AIx Max Scale
AIx Min Scale
-22 mA
22 mA
AIx Min Scale < AIx Max Scale