Parameters and firmware blocks
80
Group 02 I/O VALUES
This group contains information on the I/Os of the drive.
02
02 I/O VALUES
2.01 DI STATUS FW block: DI (page 114)
Status word of the digital inputs. Example: 000001 = DI1 is on, DI2 to DI6 are off.
2.02 RO STATUS FW block: RO (page 114)
Status of relay output. 1 = RO is energized.
2.03 DIO STATUS FW blocks: DIO1 (page 112), DIO2 (page 112), DIO3 (page 112)
Status word of digital inputs/outputs DIO1…3. Example: 001 = DIO1 is on, DIO2 and DIO3 are off.
2.04 AI1 FW block: AI1 (page 116)
Analogue input AI1 value in V or mA. The type is selected with jumper J1 on the JCU Control Unit.
2.05 AI1 SCALED FW block: AI1 (page 116)
Scaled value of analogue input AI1. See parameters 13.04 AI1 MAX SCALE and 13.05 AI1 MIN
SCALE.
2.06 AI2 FW block: AI2 (page 117)
Analogue input AI2 value in V or mA. The type is selected with jumper J2 on the JCU Control Unit.
2.07 AI2 SCALED FW block: AI2 (page 117)
Scaled value of analogue input AI2. See parameters 13.09 AI2 MAX SCALE and 13.10 AI2 MIN
SCALE.
2.08 AO1 FW block: AO1 (page 120)
Analogue output AO1 value in mA
2.09 AO2 FW block: AO2 (page 121)
Analogue output AO2 value in V
2.10 DIO2 FREQ IN FW block: DIO2 (page 112)
Frequency input value in Hz when DIO2 is used as frequency input (12.02 DIO2 CONF is set to (2)
FREQ INPUT).
2.11 DIO3 FREQ OUT FW block: DIO3 (page 112)
Frequency output value in Hz when DIO3 is used as frequency output (12.03 DIO3 CONF is set to (2)
FREQ OUTPUT).