EasyManua.ls Logo

ABB ACSM1 - Page 118

ABB ACSM1
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters and firmware blocks
118
-11…11 V / -22…22 mA Maximum AI2 input value.
13.08 AI2 MIN FW block: AI2 (see above)
Defines the minimum value for analogue input AI2. The type is selected with jumper J2 on the JCU
Control Unit.
-11…11 V / -22…22 mA Minimum AI2 input value.
13.09 AI2 MAX SCALE FW block: AI2 (see above)
Defines the real value that corresponds to the maximum analogue input value defined by parameter
13.07 AI2 MAX.
-32768…32768 Real value corresponding to value of parameter 13.07.
13.10 AI2 MIN SCALE FW block: AI2 (see above)
Defines the real value that corresponds to the minimum analogue input value defined by parameter
13.08 AI2 MIN. See parameter 13.09 AI2 MAX SCALE.
-32768…32768 Real value corresponding to value of parameter 13.08.
13.11 AITUNE FW block: None
Triggers the AI tuning function.
Connect the signal to the input and select the appropriate tuning function.
(0) NO ACTION AI tune is not activated.
(1) AI1 MIN TUNE Current analogue input AI1 signal value is set as minimum value for
AI1, parameter 13.03 AI1 MIN. The value reverts back to (0) NO
ACTION automatically.
(2) AI1 MAX TUNE Current analogue input AI1 signal value is set as maximum value for
AI1, parameter 13.02 AI1 MAX. The value reverts back to (0) NO
ACTION automatically.
(3) AI2 MIN TUNE Current analogue input AI2 signal value is set as minimum value for
AI2, parameter 13.08 AI2 MIN. The value reverts back to (0) NO
ACTION automatically.
(4) AI2 MAX TUNE Current analogue input AI2 signal value is set as maximum value for
AI2, parameter 13.07 AI2 MAX. The value reverts back to (0) NO
ACTION automatically.
AI (mA / V)
AI (real)
13.09
13.10
13.08
13.07

Table of Contents

Other manuals for ABB ACSM1

Related product manuals