121
0…22.7 mA Maximum AO1 output value.
15.04 AO1 MIN FW block: AO1 (see above)
Defines the minimum value for analogue output AO1.
0…22.7 mA Minimum AO1 output value.
15.05 AO1 MAX SCALE FW block: AO1 (see above)
Defines the real value that corresponds to the maximum analogue output value defined by
parameter 15.03 AO1 MAX.
-32768…32767 Real value corresponding to value of parameter 15.03.
15.06 AO1 MIN SCALE FW block: AO1 (see above)
Defines the real value that corresponds to the minimum analogue output value defined by
parameter 15.04 AO1 MIN. See parameter 15.05 AO1 MAX SCALE.
-32768…32767 Real value corresponding to value of parameter 15.04.
Firmware block:
AO2
(15)
Connects an actual signal to
analogue output AO2, and filters and
scales the output signal. Also shows
the value of the output.
Block outputs located in other
parameter groups
2.09 AO2 (page 80)
15.07 AO2 PTR FW block: AO2 (see above)
Selects a drive signal to be connected to analogue output AO2.
Value pointer: Group and index
15.08 AO2 FILT TIME FW block: AO2 (see above)
Defines the filtering time constant for analogue output AO2. See parameter 15.02 AO1 FILT TIME.
0…30 s Filter time constant for AO2.
15.03
15.04
15.03
15.04
15.06 15.05 15.05 15.06
AO (real)AO (real)
AO (mA)
AO (mA)
AO2
26
TLF7 2 msec (9)
< 15.07 AO2 PTR
[ SPEED ACT PERC ]
(1 / 1.02)
15.08 AO2 FILT TIME
[ 0.100 s ]
15.09 AO2 MAX
[ 10.000 V ]
15.10 AO2 MIN
[ -10.000 V ]
15.11 AO2 MAX SCALE
[ 100.000 ]
15.12 AO2 MIN SCALE
[ -100.000 ]
2.09 AO2