Parameters and firmware blocks
117
13.03 AI1 MIN FW block: AI1 (see above)
Defines the minimum value for analogue input AI1. The type is selected with jumper J1 on the JCU
Control Unit.
-11…11 V / -22…22 mA Minimum AI1 input value.
13.04 AI1 MAX SCALE FW block: AI1 (see above)
Defines the real value that corresponds to the maximum analogue input value defined by parameter
13.02 AI1 MAX.
-32768…32768 Real value corresponding to value of parameter 13.02.
13.05 AI1 MIN SCALE FW block: AI1 (see above)
Defines the real value that corresponds to the minimum analogue input value defined by parameter
13.03 AI1 MIN. See parameter 13.04 AI1 MAX SCALE.
-32768…32768 Real value corresponding to value of parameter 13.03.
Firmware block:
AI2
(13)
Filters and scales the analogue input
AI2 signal and selects the AI2
supervision. Also shows the value of
the input.
Block outputs located in other
parameter groups
2.06 AI2 (page 80)
2.07 AI2 SCALED (page 80)
13.06 AI2 FILT TIME FW block: AI2 (see above)
Defines the filter time constant for analogue input AI2. See parameter 13.01 AI1 FILT TIME.
0…30 s Filter time constant for AI2.
13.07 AI2 MAX FW block: AI2 (see above)
Defines the maximum value for analogue input AI2. The type is selected with jumper J2 on the JCU
Control Unit.
AI (mA / V)
AI (real)
13.04
13.05
13.03
13.02
AI2
24
TLF7 2 msec (7)
13.06 AI2 FILT TIME
[ 0.000 s ]
13.07 AI2 MAX
[ 10.000 mA ]
13.08 AI2 MIN
[ -10.000 mA ]
13.09 AI2 MAX SCALE
[ 100.000 ]
13.10 AI2 MIN SCALE
[ -100.000 ]
2.06 AI2
2.07 AI2 SCALED