Parameters and firmware blocks
166
Group 40 MOTOR CONTROL
Motor control settings, such as
flux reference
drive switching frequency
motor slip compensation
voltage reserve
flux optimisation
IR compensation for scalar control mode.
Flux optimisation
Flux optimisation reduces the total energy consumption and motor noise level when
the drive operates below the nominal load. The total efficiency (motor and drive) can
be improved by 1% to 10%, depending on the load torque and speed.
Note: Flux optimisation limits the dynamic control performance of the drive because
with a small flux reference the drive torque cannot be increased fast.
40
40 MOTOR CONTROL
Firmware block:
MOTOR CONTROL
(40)
This block defines motor control
settings such as
flux reference
drive switching frequency
motor slip compensation
voltage reserve
flux optimisation
IR compensation for scalar control
mode.
The block also shows the flux and
torque reference used.
Block outputs located in other
parameter groups
3.16 FLUX REF USED (page 88)
3.17 TORQUE REF USED (page 88)
40.01 FLUX REF FW block: MOTOR CONTROL (see above)
Defines the flux reference.
0…200% Flux reference.
40.02 SF REF FW block: MOTOR CONTROL (see above)
Defines the switching frequency of the drive.
When switching frequency exceeds 4 kHz, the allowed drive output current is limited. See switching
frequency derating in the appropriate Hardware Manual.
MOTOR CONTROL
31
TLF10 2 msec (9)
40.01 FLUX REF
[ 100 % ]
40.02 SF REF
[ 4 kHz ]
40.03 SLIP GAIN
[ 100 % ]
40.04 VOLTAGE RESERVE
[ 0 % ]
40.05 FLUX OPT
[ Disable ]
40.06 FORCE OPEN LOOP
[ FALSE ]
40.07 IR COMPENSATION
[ 0.00 % ]
3.16 FLUX REF USED
3.17 TORQUE REF USED